GENPACS GLOBAL MITSUBISHI RANGE – GGM
Description
GENPACS-MITSUBISHI line generator is combination between a well know engine brand name (MITSUBISHI-JAPAN) and first class alternator (LEROYSOMER-FRANCE).
GENERAL
ENGINE: MITSUBISHI-MADE BY MITSUBISHI HEAVY INDUSTRIES IN EC OR JAPAN
- Diesel 4-cycle, Direct Injection, Electric governor, Fuel Pump, Electric Start c/w battery charging alternator.
- Aspiration: Turbo Charged.
- Steady state speed stability at any constant load is 0.25% or better.
- Water Cooling by tropical radiator and self-driven fan.
- Exhaust Emission: EU Standard Stage II/ Tier 3.
- Easy Replaceable Filters (Oil, Fuel and Air).
- Fuel type: Standard Diesel Oil.
- GENUINE MITSUBISHI ENGINE (MADE IN EU OR JAPAN)
- Global Mitsubishi Warranty
- Manufacture Standard: ISO 8528/1; ISO 3046/1; BS 5514/1; BS 2869 Class A1 + A2
ALTERNATOR: BRAND NAME: LEROYSOMER (FRANCE)– MADE IN EU
- Synchronous, Brushless, IP23, Insulation Class H, 4P, 1500 RPM-50Hz
- Standard Temperature Rise is 125 ºC, Temperature Rise up to 163 ºC.
- Standard AC Voltage: 380V/220V, 400V/230V.
- Operation Environment: tropical condition with altitude < 1000m.
- Colling type: By direct fan.
- Excitation system: AREP, PMG, AREP + PMI.
- Self auto Excited.
- Voltage Control by AVR with variation at max. ± 0.5-1%.
- TIF < 50, Wave Form IEC THF < 2%.
- Total Harmonic distortion THD (**) < 4 %.
- Over Speed 2250 RPM within 2 minutes.
- Short Circuit 300% within 10s.
- Manufacture Standard: EN 61000-6-3, EN 61000-6-2, EN 55011 Group 1 class B standard for European Zone (CE marking), ISO 9001, ISO 14001, IEC 60034, NEMA MG 1.32-33, ISO 8528-3, CSA C22.2 n°100-14, UL 1446 (UL 1004 on request).
CONTROL PANEL: BRAND NAME: DEEPSEA (UK) – MODEL DSE 7320MKII- MADE IN UK
Features:
- Controlling Generator, Auto Mains Failure (AMF) and ready to connect to any ATS.
- Remote Control Available.
- Standard connection by RS232 and RS485 port.
- BMS connection support.
- Synchronizing Connection Available.
- Voltage adjuster.
- Speed adjuster.
- Fuel level monitoring and low level alarm.
- Load coming/cut off indication.
- Indication and Metering by LCD and LED.
- Recording Fault, Starts.
- Fuel Pump Control.
- Emergency Stop Button on Control Panel and on Soundproof.
- Generator Metering: 3-phase Voltage, 3-phase Current, Frequency, Rotation, Oil Pressure, Water Temperature, Battery Voltage, DC voltage, Run-hour, KW, KWh, KVA, KVAh, KVAr, KVARh, Power Factor, fuel level.
- Mains Metering: Frequency, Voltage.
Alarm and Protection:
Alarm and Shut-down: High Water Temperature, Low Oil Pressure, Over or Under Frequency/ Rotation, Over/Under AC Voltage, Over Current, Exceed Power, Short Circuit, Emergency Stop Button Pressed, Start Fault, Over Cranking.
Alarm: Charging Failure, Over/Under Battery Voltage, Exceed Maintenance Schedule
STANDARD ACCESSORIES:
- Heavy duty Base Frame with Anti-Vibration Rubbers.
- Heavy Duty Batteries and AC Charger Available.
- Fuel Day Tank on Base Frame up to 500KVA Prime Power.
- MCCB up to 800A for 500KVA Prime Power.
- Technical Documents.
NOTES:
- Output Power is in accordance with ISO8528 at temperature up to 45ºC with average equal up to 35ºC, maximum altitude up to 1000m from sea level, humidity up to 100%, average equal up to 85%.
- Standby Power is maximum power available for the duration of any power outage at variable load. No overload is allowed.
- Prime Power is available for continuous operation at variable load. The average output power during 24h period of operation must not exceed 80% of the Prime Power. 10% over load is allowed in 1h with every 12h of operation.
ADVANTAGED FEATURES:
- The quality of GENPACS-MITSUBISHI LINE generator is guaranteed as the highest EU standard.
- Mitsubishi and alternator c/w Certificate of Quality of Manufacturer.
- Generator is tropicalized for operation on tropical conditions.
- Generator is available tested at full load before delivery under ISO8528 and DIN6271.
- Independent Test and Inspection are available on request.
- Quality Product is controlled by ISO 9001:2008 and ready to upgrade to ISO 9001:2015.
OTHER OPTIONS:
- Genpacs Auto Transfer Switch 800A to 4000A equipped by ACB.
- Genpacs Auto Synchronizing Panel for max 12 generators up to 2,750 KVA per set.
- Wireless remote control feature by 3-4G network
- Genpacs Sound Proof: Below 70 Db (A) at 7m distance.
SOUNDPROOF for GENERATOR: